logo
Send Message
English
Achievers Automation Limited

Achievers makes all your needs Achievable!

Home ProductsPEPPERL FUCHS Isolated Barrier

Pepperl+Fuchs KFU8-UFC-1.D Frequency Converter With Trip Values

I'm Online Chat Now

Pepperl+Fuchs KFU8-UFC-1.D Frequency Converter With Trip Values

Pepperl+Fuchs KFU8-UFC-1.D Frequency Converter With Trip Values
Pepperl+Fuchs KFU8-UFC-1.D Frequency Converter With Trip Values Pepperl+Fuchs KFU8-UFC-1.D Frequency Converter With Trip Values Pepperl+Fuchs KFU8-UFC-1.D Frequency Converter With Trip Values Pepperl+Fuchs KFU8-UFC-1.D Frequency Converter With Trip Values

Large Image :  Pepperl+Fuchs KFU8-UFC-1.D Frequency Converter With Trip Values

Product Details:
Place of Origin: Germany
Brand Name: PF
Certification: ATEX
Model Number: KFU8-UFC-1.D
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: Negotiate
Packaging Details: carton
Delivery Time: stock
Payment Terms: T/T, Alipay, Paypal
Supply Ability: 100pcs per month
Detailed Product Description
Manufacture: Pepperl+Fuchs Model: KFU8-UFC-1.D
Input Resistance: 4.7 KΩ Pulse Duration: > 50 µs
Input Frequency: 0.001 ... 10000 Hz Current Range: 0 ... 20 MA Or 4 ... 20 MA
Open Loop Voltage: Max. 24 V DC Mass: 300 G
Highlight:

Pepperl+Fuchs kfu8 ufc 1 d

,

kfu8 ufc 1 d Frequency Converter

,

pepperl fuchs kfu8 ufc 1 d

Product Details:
Manufacturer : Pepperl+Fuchs
Product No. : KFU8-UFC-1.D
Product Type : Frequency Converter with Trip Values
 
Features:

  • 1-channel signal conditioner
  • Universal usage at different power supplies
  • Input for 2- or 3-wire sensors, NAMUR sensors or dry contacts
  • Input frequency 1 mHz ... 10 kHz
  • Current output 0/4 mA ... 20 mA
  • Relay contact and transistor output
  • Start-up override
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511

Technical data

1. General specifications
    Signal type: Digital Input
2. Functional safety related parameters
    Safety Integrity Level (SIL): SIL 2
3. Supply
    Connection: terminals 23, 24
    Rated voltage: 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
    Power dissipation/power consumption: ≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA
4. Interface
    Programming interface: programming socket
5. Input
    Connection side: field side
    Connection: Input I: 2-wire sensor: terminals 1+, 3- three wire sensor: terminals 1+, 2- and 3
                        input II: terminals 13+, 14- start-up override;
    Input I: 2- or 3-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
       Open circuit voltage/short-circuit current: 22 V / 40 mA
       Input resistance: 4.7 kΩ
       Switching point/switching hysteresis: logic 1: > 2.5 mA ; logic 0: < 1.9 mA
       Pulse duration: > 50 µs
       Input frequency: 0.001 ... 10000 Hz
       Line fault detection: breakage I ≤ 0.15 mA; short-circuit I > 4 mA
    Input II: startup override: 1 ... 1000 s, adjustable in steps of 1 s
       Active/Passive: I > 4 mA (for min. 100 ms) / I < 1.5 mA
       Open circuit voltage/short-circuit current: 18 V / 5 mA
6. Output
    Connection side: control side
    Connection: output I: terminals 10, 11, 12
                        output II: terminals 16, 17, 18
                        outout III: terminasl 19+, 20-
                        output IV: terminals 8+, 7-
    Output I, II: signal, relay
       Contact loading: 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
       Mechanical life: 5 x 107 switching cycles
       Energized/De-energized delay: approx. 20 ms / approx. 20 ms
    Output III: electronic output, passive
       Contact loading: 40 V DC
       Signal level: 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof)
       0-signal: blocked output (off-state current ≤ 10 µA)
    Output IV: analog
       Current range: 0 ... 20 mA or 4 ... 20 mA
       Open loop voltage: max. 24 V DC
       Load: max. 650 Ω
       Fault signal: downscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43)
7. Indicators/settings
    Display elements: LEDs , display
    Control elements: Control panel
    Configuration: via operating buttons
                           via PACTware
    Labeling: space for labeling at the front
8. Conformity
    Electromagnetic compatibility: NE 21:2006
    Degree of protection: IEC 60529:2001
9. Ambient conditions
    Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
10. Mechanical specifications
    Degree of protection: IP20
    Connection: screw terminals
    Mass: 300 g
    Dimensions: 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
       Height: 119 mm
       Width: 40 mm
       Depth: 115 mm
    Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001

 

Pepperl+Fuchs KFU8-UFC-1.D Frequency Converter With Trip Values 0   Pepperl+Fuchs KFU8-UFC-1.D Frequency Converter With Trip Values 1

 

Related Models:

KCD2-SCD-EX1 NBB5-18GM50-E2-V1
KCD2-STC-EX1.20 NBB8-18GM60-A2-V1
KFA6-DWB-EX1.D NBN3-F25F-E8-V1
KFA6-SR2-Ex2.W NBN40-U1K-N0
KFD0-CS-Ex1.50P NBN40-U4LK-N0
KFD0-HMS-16 NBVB15-U1.Z2
KFD0-RSH-1.4S.PS2 NCB5-18GM40-NO
KFD0-SD2-EX1.10100 NJ10-30GM-N-5M
KFD0-SD2-EX1.1045 NJ15-30GK-N
KFD2-UT2-1 NJ2-12GK-SN
KFD2-CD-1.32 NJ2-12GM-N
KFD2-CD-EX1.32 NJ4-12GK-SN
KFD2-HMM-16 NJ5-18GK-N
KFD2-SH-EX1.T NJ5-18GK-N-150
KFD2-SH-Ex1.T.OP NJ5-18GM-N
KFD2-SL2-EX2.B NJ8-18GK-N
KFD2-SR2-EX1.W RD0-FB-EX4
KFD2-SR2-Ex2.W RD0-FB-EX4.COM
KFD2-STC5-1.2O SC3,5-G-N0
KFD2-STC5-Ex1 SC3,5-G-N0-5M
KFD2-STC5-Ex1.H SC3,5-G-N0-6M
KFD2-UT2-1 SJ3,5-N
KFD2-VR4-EX1.26 SJ3,5-S1N
KFU8-UFC-1.D UPR-03
KFU8-UFT V15-G-2M
K-HM26-2M-261533 Z 787
NBB15-U1-E2 Z787.H
NBB15-U1-Z2 HIC2031

 
Company Introduction:
Achievers Automation Limited has more than 10 years experience in the market of Industrial Automation, specialized in reselling factory sealed Probe, Sensor, DCS,isolator barrier, HMI, PLC,Adapter,Profibus connector and cable from Brands as BENTLY NEVADA, Endress+Hauser, YOKOGAWA,MTL,Allen-Bradley, Pepperl+Fuchs,Rosemount, ASCO, Schneider, Lenze, Pro-face, Mitsubishi, Omron, Lenze, Delta, Honeywell, Siemens and etc. If you have any request, please do not hesitate to contact us.
 
FAQ of Achievers
Q:Are the Products Genuine OEM Units?
A: These items have been certified by Achievers Automation Limited to be genuine OEM Units obtained through OEM or independent third-party channels.
Q:How will you arrange shipment?
A: We can arrange shipment based on your request. We have cooperated forwader who can arrange shipment via FedEx, DHL,TNT with good price.
Q:What is the warranty of goods?
A: One-year Warranty.

 

Contact Details
Achievers Automation Limited

Contact Person: Caroline Chan

Tel: 13271919169

Send your inquiry directly to us (0 / 3000)