MTL5516C MTL Instruments Switch/Proximity Detector Interface
The MTL5516/C enable two safe-area loads to be controlled by a switch
or proximity detector located in a hazardous-area. When selected, open
or short circuit conditions in the field wiring are detected by the linefault-detect (LFD) facility and also indicated on the top of the module.
Phase reversal for each channel is selected by a switch on the side of
the module and output is provided by changeover relay contacts.
circuit in either field circuit.
SPECIFICATION
See also common specification
• Number of channels
Two
• Location of switches
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
• Location of proximity detector
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
• Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
• .Voltage applied to sensor
7 to 9V dc from 1kΩ ±10%
• Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200µA (650Ω) nominal
• Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. Line faults are indicated by an LED for each channel. The channel output relay is
de-energised if an input line fault is detected.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch
• Safe-area output
Two single-pole relays with changeover contacts
Note: reactive loads must be adequately suppressed
• Relay characteristics
Response time: 10ms maximum
Contact rating(Safe Area):
250V ac, 2A, cosØ >0.7,
40V dc, 2A, resistive load
Contact rating(Zone 2):35V, 2A, 100VA.
• Maximum current consumption
35mA at 24V
11.Power dissipation within unit
0.84W at 24V
• LED indicators
Green: power indication
Yellow: two: channel status, on when output energised
Red: two: LFD indication, on when line fault detected
• Safety description (each channel)
Uo=10.5V Io=14mA Po=37mW Um = 253V rms or dc
Related Models:
HCU16 | MTL5521 | MTL4544 |
HCU3700 | MTL5522 | MTL4544D |
HM64RIB20-1.0 | MTL5531 | MTL4546Y |
HM64RIB20-1.5 | MTL5532 | MTL4549Y |
HMM64 | MTL5541 | MTL4573 |
HMRIB16-1.0 | MTL5541S | MTL4575 |
HMS64 | MTL5544 | MTL4646Y |
HTP-SC32 | MTL5544D | MTL4850 |
MTL4044D | MTL5546 | MTL4851 |
MTL4511 | MTL5546Y | MTL4852 |
MTL4516 | MTL5561 | MTL5018 |
MTL4516C | MTL5573 | MTL5032 |
MTL4521 | MTL5575 | MTL5042 |
MTL4541 | MTL5582B | MTL5044 |
MTL4541 | MTL7728+ | MTL5049 |
Frequently Asked Questions
Q:Are the Products Genuine OEM Units?
A: These items have been certified by Achievers Automation Limited to be genuine OEM Units obtained through OEM or independent third-party channels.
Contact Person: Caroline Chan
Tel: 13271919169